    RTD/TC Input Digital Signal Isolator Analog Output 0-5V 4-20mA Converter 24V DC

    Ask Lasest Price
    Brand Name : LS
    Model Number : THS-TPXX
    Certification : CE
    Price : negociate
    Payment Terms : T/T, Western Union, Paypal
    Supply Ability : 10000pcs
    Delivery Time : 3-6 days
    • Product Details
    • Company Profile

    RTD/TC Input Digital Signal Isolator Analog Output 0-5V 4-20mA Converter 24V DC

    Input

    Input signal: PT100, Cu50, Ni1000 and other thermal resistance; B, E, J, K, N, R, S, T and other thermocouples; voltage (maximum range 0-10V); millivolts (maximum range 0-100mV); Current source (4- 20mA); transmitter (distribution), current 4-20mA; resistor, potentiometer (maximum range 0-2K)

    Distribution voltage: ≥16V

    Measuring range: depending on the type of sensor used


    Output

    Output signal: 4-20mA; 0-20mA; 0-5V; 0-10V

    Output load resistance: RL ≤ 500Ω (when the output is a current signal); RL ≥ 10KΩ (when the output is a voltage signal)


    Basic parameters

    Power supply: DC24V, ±10%

    Current consumption: ≤50mA (one input and one output 24V power supply, 20mA output); ≤70mA (one input and two output, 24V power supply, 20mA output)

    Basic accuracy: 0.1% F.S.

    Response time: 0.5S

    Insulation strength: 1500V AC / 1min (between input, output, and power)

    Insulation resistance: ≥100MΩ (between input, output, and power)

    Operating temperature range: -20~+55 degrees

    Electromagnetic compatibility: in accordance with GB/T 18268 (IEC61326-1)


    Parameter
    THS-TPXXXmarks
    Configuration11 input 1 output
    21 input 2 output
    Input signalU

    General signal input

    (RTD, TC, Potentiometer)

    Please indicate signal type and measure range

    Output signal14-20mA
    20-20mA
    40-5V
    60-10V
    Please indicate your required input type and output type when place order

    Dimension


    How to wire



    Quality RTD/TC Input Digital Signal Isolator Analog Output 0-5V 4-20mA Converter 24V DC for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Shenzhen Qianhai Lensen Technology Co., Ltd
    *Subject:
    *Message:
    Characters Remaining: (0/3000)